GXT5 UPS 5000VA/5000W 208 120 50 & 60HZ - Vertiv
Battery Information |
Battery Chemistry |
Lead Acid |
Hot Swappable |
Yes |
Backup/Run Time (Half Load) |
12.50 Minute |
Backup/Run Time (Full Load) |
4.50 Minute |
Battery Characteristics |
Valve-regulated, Non-spillable, Flame-retardant |
Replaceable Battery |
Yes |
Number of External Battery Cabinets |
1 |
Backup/Run Time With External Battery Cabinet (Full Load) |
12.50 Minute |
Backup/Run Time With External Battery Cabinet (Half Load) |
33 Minute |
Controls/Indicators |
Status Indicators |
LED/Full Color Graphic LCD |
Environmental Conditions |
Maximum Operating Temperature |
40°C |
Maximum Operating Elevation |
3 km |
Environmental Sensors |
Leak Detection Sensor |
Environmental Sensors |
Humidity Sensor |
Environmental Sensors |
Temperature Sensor |
Interfaces/Ports |
USB |
Yes |
VGA |
No |
Network (RJ-45) |
Yes |
Modem (RJ-11) |
No |
Serial Port |
Yes |
Total Number of Expansion Slots |
1 |
Miscellaneous |
Additional Information |
- Package Type: Natrual corrugated with single color silk screen
- Dataline Protection: No
|
TAA Compliant |
No |
Energy Star |
Yes |
Physical Characteristics |
Weight (Approximate) |
56.97 kg |
Form Factor |
Rack/Tower |
Rack Height |
4U |
Height |
172.7 mm |
Width |
429.3 mm |
Depth |
650.2 mm |
Power Description |
Output Voltage |
120 V AC |
Output Voltage |
208 V AC |
Waveform Type |
Pure Sine Wave |
Input Frequency |
60 Hz |
Load Capacity (VA) |
5 kVA |
User Selectable Output |
208/120VAC |
Utility (AC) Mode Overload |
- 105% to 125% for 5 minutes
- 125% to 150% for 60 seconds
- >150% (impact load) minimum 200 ms
|
Technical Information |
Application/Usage |
IT System |
Application/Usage |
Mission Critical Equipment |
Application/Usage |
Data Center |
Bypass Switch |
Automatic & Manual |
Bypass Switch |
Internal |
Bypass Switch |
Maintenance |
Emergency Power OFF |
Yes |
Phase |
Single Phase |
Receptacle Type |
Hardwired |
Transfer Time |
0 ns |