VERTIV LIEBERT GXT5 ON-LINE 500VA/500W 1 - Vertiv
| Battery Information |
| Battery Life |
5 Year |
| Battery Chemistry |
Lead Acid |
| Hot Swappable |
Yes |
| Battery Size |
12V |
| Hot Pluggable |
Yes |
| Number of Batteries |
3 |
| Backup/Run Time (Half Load) |
36.50 Minute |
| Backup/Run Time (Full Load) |
15 Minute |
| Battery Characteristics |
Valve-regulated, Non-spillable |
| Typical Battery Recharge Time |
3 Hour |
| Number of External Battery Cabinets |
1 |
| Backup/Run Time With External Battery Cabinet (Full Load) |
1.08 Hour |
| Backup/Run Time With External Battery Cabinet (Half Load) |
2.20 Hour |
| Controls/Indicators |
| Status Indicators |
Color LCD |
| Environmental Conditions |
| Maximum Operating Temperature |
40°C |
| Maximum Operating Elevation |
3 km |
| Maximum Storage Elevation |
15 km |
| Environmental Sensors |
Humidity Sensor |
| Environmental Sensors |
Temperature Sensor |
| Environmental Sensors |
Leak Detection Sensor |
| Interfaces/Ports |
| VGA |
No |
| Modem (RJ-11) |
No |
| Serial Port |
Yes |
| EPO Port |
Yes |
| USB (HID Compliant) Port |
Yes |
| Miscellaneous |
| Additional Information |
- Operating Temperature,°F (°C):+32 to +104 (0 to 40)
- Storage Temperature,°F (°C ):-4 to +140 (-20 to 60) contain batteries will be from -15 to 40°C.
- Relative Humidity:0% to 95%, non-condensing
- Audible Noise:
- <46dBA max @ 3 ft. (1m) front and sides
- <43dBA, at 3 ft. (1m) rear
|
| Assembly Required |
No |
| TAA Compliant |
No |
| Energy Star |
Yes |
| Physical Characteristics |
| Weight (Approximate) |
16.78 kg |
| Form Factor |
Rack/Tower |
| Rack Height |
2U |
| Height |
86.4 mm |
| Width |
429.3 mm |
| Depth |
398.8 mm |
| Product Color |
Black |
| Color Family |
Black |
| Power Description |
| Circuit Breaker |
Yes |
| Output Voltage |
120 V AC |
| Input Current |
6 A |
| Waveform Type |
Sine Wave |
| Output Current |
4.20 A |
| Input Voltage Range |
60 V AC - 150 V AC |
| Input Frequency |
70 Hz |
| Load Capacity (VA) |
500 VA |
| Load Capacity (Watt) |
500 W |
| User Selectable Output |
Typical 120V User Selectable Output: 110/115/120/125VAC (user-configurable); ±3% |
| Utility (AC) Mode Overload |
- >200% for 250ms
- 150- 200% for 50 seconds
- 125- 150% for 60 seconds
- 105-125% for 60 seconds
|
| Technical Information |
| Application/Usage |
Mission Critical Equipment |
| Application/Usage |
IT Equipment |
| Emergency Power OFF |
Yes |
| Cord Length |
3.05 m |
| Phase |
Single Phase |
| Receptacle Type |
NEMA 5-15R |
| Transfer Time |
0 ns |
| Receptacle Detail |
6 x NEMA 5-15R |